MbusMasterFunctionsreadMultipleMod10000 Method (Int32, Int32, Int32)

Modbus function 3 (03 hex) for 32-bit modulo-10000 long int data types, Read Holding Registers/Read Multiple Registers as modulo-10000 long int data.

Namespace:  FieldTalk.Modbus.Master
Assembly:  FieldTalk.Modbus.Master (in FieldTalk.Modbus.Master.dll) Version: 2.15.2-eval+3d8362b4bb861c05760d48b11d303e954bb8597c
Syntax
public int readMultipleMod10000(
	int slaveAddr,
	int startRef,
	int[] int32Arr
)

Parameters

slaveAddr
Type: SystemInt32
Modbus address of slave device or unit identifier (Range: 1 - 255)
startRef
Type: SystemInt32
Start reference (Range: 1 - 65536)
int32Arr
Type: SystemInt32
Buffer which will be filled with the data read. The length of the array determines how many values are read (Range: 1-62).

Return Value

Type: Int32
BusProtocolErrors.FTALK_SUCCESS on success or error code. See BusProtocolErrors for possible error codes.
Remarks
Reads the contents of pairs of consecutive output registers (holding registers, 4:00000 table) representing a modulo-10000 long int value into 32-bit int values and performs number format conversion.
Note Note
Modbus does not know about any other data type than discretes and 16-bit registers. Because a modulo-10000 value is of 32-bit length, it will be transferred as two consecutive 16-bit registers. This means that the amount of registers transferred with this function is twice the amount of int values passed to this function.
Note Note
No broadcast supported