MbusSlaveServersetTimeout Method

Configures master transmit time-out supervision.

Namespace:  FieldTalk.Modbus.Slave
Assembly:  FieldTalk.Modbus.Slave (in FieldTalk.Modbus.Slave.dll) Version: 2.11.0-eval+eb1ecbe71c969eff5d7c05d58da16dade0474678
Syntax
public int setTimeout(
	int timeOut
)

Parameters

timeOut
Type: SystemInt32
Timeout value in ms (Range: 1 - 100000), 0 disables time-out

Return Value

Type: Int32
BusProtocolErrors.FTALK_SUCCESS on success or error code. See BusProtocolErrors for possible error codes.
Remarks
Configures master transmit time-out supervision. The slave can monitor whether a master is actually transmitting characters or not. This function sets the transmit time-out to the specified value. A value of 0 disables the time-out, which stops time-out notifications being sent to the Data Provider.
Note Note
The time-out value is a minimum value only and the actual time may be longer. How precise it is followed depends on the operating system used, its scheduling priority and its system timer resolution.
Note Note
The time-out does not check whether a master is sending valid frames. The transmission of characters is sufficient to avoid the time-out.