MbusMasterFunctions.readInputLongInts Method (Int32, Int32, Int32[])

Modbus function 4 (04 hex) for 32-bit long int data types, Read Input Registers as long int data

[Visual Basic]
Overloads Public Function readInputLongInts( _
   ByVal slaveAddr As Integer, _
   ByVal startRef As Integer, _
   ByVal int32Arr As Integer() _
) As Integer
[C#]
public int readInputLongInts(
   int slaveAddr,
   int startRef,
   int[] int32Arr
);

Parameters

slaveAddr
Modbus address of slave device or unit identifier (Range: 1 - 255)
startRef
Start reference (Range: 1 - $10000)
int32Arr
Buffer which will be filled with the data read. The length of the array determines how many values are read (Range: 1-62).

Return Value

BusProtocolErrors.FTALK_SUCCESS on success or error code. See BusProtocolErrors for possible error codes.

Remarks

Reads the contents of pairs of consecutive input registers (3:00000 table) into 32-bit long int values.

Note    Modbus does not know about any other data type than discretes and 16-bit registers. Because a long int value is of 32-bit length, it will be transferred as two consecutive 16-bit registers. This means that the amount of registers transferred with this function is twice the amount of int values passed to this function.
Note    No broadcast supported